An 18/17 kW Generac standby generator:
John in Ocean, NJ had Green Sun Energy Services install a Generac 18/17 kW natural-gas standby generator in November of 2026. The home is served by a 200-amp electrical service, and the system was sized for 2,400 square feet of living space.
The transfer arrangement is a managed whole-house setup using a Generac 200-amp Service Entrance Rated Automatic Transfer Switch with an Integrated Surge Protection Device (Model G0099280). When JCP&L power goes out, the switch detects the outage and signals the generator to start, then transfers the full load automatically. Because it is a whole-house configuration, John does not have to decide which circuits stay live — everything comes back on. One Load Management Module is wired in to handle one 60-amp device; if the generator’s demand approaches its limit while that load is running, the module sheds it automatically and restores it when capacity allows, all without any manual intervention.
The generator itself is the Generac Next Generation Air-Cooled model, Model 7259, rated at 18 kW on liquid propane and 17 kW on natural gas — here running on natural gas. Connectivity is built in: the unit includes cellular, Wi-Fi, and Bluetooth connectivity so John can monitor status and receive alerts remotely. The generator sits on a 5,000 PSI precast concrete pad (54″ x 32″ x 3″, 190 lbs) and starts from a 12-volt battery.
The electrical work included up to 20 feet of electrical run and 20 feet of plumbing. Grounding followed NJAC 5:23-3.16, which required two grounding rods and an intersystem bonding bridge, a #4 AWG green-jacket copper ground wire, and a #4 AWG copper bond from the water main to the service main.
The installation is covered by a 5-year limited warranty from Generac and a 5-year limited workmanship warranty from Green Sun Energy Services. John also has a service plan in place that includes an annual maintenance visit and an extended parts-and-labor warranty, so the generator will be looked after on a regular schedule going forward.
Why Ocean homeowners choose Green Sun Energy Services
Complete backup power, from sizing and installation to the service that keeps it ready.
What makes Green Sun Energy Services different
- Standby generators: installed and serviced as a Generac Authorized Sales and Service Dealer, by factory-authorized Generac technicians. On this home: a Generac 7259 standby generator (18 kW LP / 17 kW NG) running on natural gas, on a 200-amp transfer switch (managed whole house) and serviced by Green Sun Energy Services.
- Warranty: backed by a 5-year generator workmanship warranty.
- Local: locally owned and operated in New Jersey since 2010, NJHIC licensed (#13VH06229000), with 449 completed standby generator projects across Monmouth County and 626 standby generator projects throughout New Jersey.
Our work in Ocean
Green Sun Energy Services has completed 8 standby generator installations and 12 generator service customers in Ocean and 924 projects in Monmouth County. Ocean, a township in Monmouth County, is served by JCP&L.
Thinking about a standby generator for your Ocean home? Tell us about your project here or call 732-410-7818.
Power it. Protect it. Maintain it.
Project Facts
- Location
- Ocean, NJ
- Services
- Standby Generator Installation, Standby Generator Service
- Client since
- November 2026
- Manufacturer & model
- Generac 7259
- Rated output
- 18 kW LP / 17 kW NG
- Fuel
- Natural Gas
- Home sized for
- 2,400 sq ft
- Electrical service
- 200 amp
- Transfer switch
- 200 amp
- Load management
- Managed Whole House
- Workmanship warranty
- 5 years
Standby generator questions from Ocean homeowners
Does new gas piping have to be pressure tested in Ocean?
Yes. Gas piping subject to the adopted fuel-gas code must be inspected and tested before it is accepted. New Jersey adopts the 2024 International Fuel Gas Code, which governs the inspection, the test pressure and how long the test has to hold.
What happens if we add a heat pump, a pool or an EV charger later?
Any major new electrical load should prompt a review of the generator's capacity. A machine sized correctly at installation may no longer be adequate once substantial loads are added. Load management can often accommodate the new equipment without replacing the generator.
Can a generator sit on compacted stone?
Certain air-cooled models can, on a properly prepared compacted aggregate base, where the applicable installation manual permits it. The base has to be stable, level, and resistant to settling and erosion, and the preparation comes from the model's own manual rather than from general practice.